Understanding the boiler size calculator — concept and principle
This calculator estimates the boiler output needed in kW and BTU/h to heat a home and provide hot water, for a combi boiler that heats tap water on demand or a system boiler that reheats a stored cylinder. Homeowners use it to check installer recommendations.
How it is calculated
Space heating = design heat loss × (1 + margin %)
Combi hot water: P (kW) = flow (L/min) ÷ 60 × 4.186 × (T_hot − T_cold); boiler size = larger of heating and hot water
System boiler: P = cylinder litres × 4.186 × (T_store − T_cold) ÷ (reheat minutes × 60); boiler size = heating + hot water
1 kW = 3,412.14 BTU/h
The principle
Heating water takes energy equal to mass × specific heat × temperature rise; water's specific heat is about 4.186 kJ per kg per °C, and 1 L weighs about 1 kg. A combi boiler must heat running water instantly, which needs far more power than most homes need for radiators, and it pauses heating while doing so. A system boiler stores hot water, so its hot water demand is spread over the reheat time but adds to heating.
Worked example
Default inputs: heat loss 8 kW, margin 10%, combi, flow 10 L/min, cold 10 °C, hot 45 °C.
- Space heating = 8 × 1.10 = 8.8 kW.
- Hot water = 10 ÷ 60 × 4.186 × (45 − 10) = 24.4 kW.
- Combi size = larger value = 24.4 kW, set by hot water.
- In BTU/h = 24.42 × 3,412.14 = 83,319.
| Combi: hot-water temperature at the tap (°C) | Boiler output needed (kW) |
|---|---|
| 11.2 | 8.8 |
| 22.5 | 8.8 |
| 33.8 | 16.6 |
| 45 | 24.4 |
| 56.2 | 32.3 |
| 67.5 | 40.1 |
| 90 | 55.8 |
How to read the result
For combis the hot water flow usually sets the size; a higher flow or colder mains water in winter needs a bigger boiler. For system boilers, a longer reheat time allows a smaller boiler. Oversizing a boiler for heating can make it cycle on and off, reducing efficiency.
Common mistakes
- Guessing heat loss instead of using a room-by-room calculation.
- Using summer mains water temperature.
- Expecting a combi to supply two showers at once at full flow.
Frequently asked questions
What size combi boiler do I need?
It is usually set by the hot water flow you want; about 24–35 kW is common for homes.
Why is hot water so demanding?
Heating running water from 10 °C to 45 °C at 10 L/min needs over 24 kW.
How do I find my heat loss?
A heating engineer can calculate it room by room using a standard method such as EN 12831.
Sources: OpenStax, University Physics Volume 2, 2016, §1.4 (specific heat of water 4,186 J/(kg·°C)) · EN 12831-1:2017, Energy performance of buildings — Method for calculation of the design heat load