Understanding the heat loss calculator — concept and principle
This calculator estimates how much heat a building loses through its walls, windows, roof and floor and through ventilation, at the coldest design temperature, and the heating energy needed over a year. Use it to size a heater or heat pump, compare insulation upgrades, or see where most heat escapes.
How it is calculated
- Fabric loss for each part = U × A × ΔT, with U the U-value (W/m²K), A the area (m²) and ΔT = inside − outside temperature.
- Ventilation loss = n × V × 1,200 ÷ 3,600 × ΔT, about 0.33 × n × V × ΔT, with n air changes per hour and V the heated volume.
- Heat loss coefficient H (W/K) = Σ U·A + ventilation part.
- Design heat loss = H × ΔT.
- Yearly heating energy (kWh) = H × heating degree days × 24 ÷ 1,000.
The principle
Heat flows from warm to cold at a rate proportional to the temperature difference. The U-value says how many watts pass through one square metre for each degree of difference, so lower U-values mean better insulation. Air that leaks out or is ventilated takes its heat with it: warming one cubic metre of air by one degree takes about 1,200 joules. Adding all paths gives H, the building's total loss per degree. On the coldest design day, H times the temperature difference is the heater output needed.
Worked example
Default inputs: walls 80 m² at 0.35, windows and doors 15 m² at 1.6, roof 60 m² at 0.2, floor 60 m² at 0.25, volume 300 m³, 0.5 air changes, 20 °C inside, −10 °C outside, 2,800 degree days.
- ΔT = 20 − (−10) = 30 K.
- Walls 80 × 0.35 × 30 = 840 W; windows 15 × 1.6 × 30 = 720 W; roof 360 W; floor 450 W.
- Ventilation = 0.5 × 300 × 1,200 ÷ 3,600 = 50 W/K × 30 = 1,500 W.
- H = 28 + 24 + 12 + 15 + 50 = 129 W/K; design loss = 129 × 30 = 3,870 W.
- Yearly energy = 129 × 2,800 × 24 ÷ 1,000 = 8,669 kWh.
| Inside temperature (°C) | Design heat loss (W) |
|---|---|
| 5 | 1,935 |
| 10 | 2,580 |
| 15 | 3,225 |
| 20 | 3,870 |
| 25 | 4,515 |
| 30 | 5,160 |
| 40 | 6,450 |
How to read the result
The breakdown shows where to act first. Here ventilation is the largest single loss, so draught-proofing or heat-recovery ventilation may pay off before more insulation. The design loss is the heater output needed on the coldest day; the yearly energy, divided by the system efficiency or heat pump COP, estimates fuel or electricity use.
Common mistakes
- Counting window area twice, in the walls and the windows.
- Using centre-of-glass U-values instead of whole-window values.
- Guessing air changes; older houses leak much more than new ones.
- Using a design temperature from a different climate.
Frequently asked questions
How do I calculate heat loss of a room?
Add U × A for every surface, add 0.33 × air changes × volume, and multiply by the temperature difference.
What is a U-value?
The heat flow through one square metre for each degree of temperature difference, in W/m²K.
How big a heat pump do I need?
Roughly the design heat loss at your coldest design temperature; a professional calculation is recommended.
Sources: ISO 13789:2017, Thermal performance of buildings — Transmission and ventilation heat transfer coefficients · EN 12831-1:2017, Energy performance of buildings — Method for calculation of the design heat load