Breaker Size Calculator (US NEC 125% rule & standard ampere ratings)

Results update as you type.

Your numbers

Understanding the circuit breaker size calculator — concept and principle

This calculator estimates the minimum circuit breaker rating for a load under the US National Electrical Code rule for continuous and non-continuous loads, then rounds up to the next standard breaker size. It handles DC, single-phase and three-phase supplies.

3,600 W continuous load on 240 V3,600 W continuous load on 240 V3,600 W continuous load on 240 Vload current15 A× 1.25 minimum18.75 Astandard breaker20 ABreaker 75% loaded · wire must suit 20 A
A continuous load is sized at 125% of its current, so 15 A needs at least 18.75 A: the next standard size is 20 A.

How it is calculated

The principle

A thermal-magnetic breaker heats up with current. Standard breakers in an enclosure are not rated to carry their full nameplate current continuously, so the code requires a 25% margin for loads that run for hours. Requiring 125% of the continuous current is the same as loading a breaker to no more than 80%. The breaker protects the wire, so the wire must also be rated for the chosen breaker.

Worked example

Default inputs: 3,600 W, single-phase, 240 V, power factor 1, continuous load.

  1. Load current = 3,600 ÷ (240 × 1) = 15 A.
  2. Minimum rating = 15 × 1.25 = 18.75 A.
  3. Next standard size = 20 A.
  4. Breaker loading = 15 ÷ 20 = 75%.
  5. Also check: the wire must be rated for the breaker (in this case a conductor rated for 20 A).
How Standard breaker size (A) changes with Voltage (V)How Standard breaker size changes with V…02040608060120180240300360480Example: 20Voltage (V)
Each point is the calculator re-run with only “Voltage (V)” changed; the gold point is the default example. Change the inputs above and this chart follows your numbers.
Voltage (V)Standard breaker size (A)
6080
12040
18025
24020
30015
36015
48015

How to read the result

The result is the smallest standard breaker allowed for the load; a larger breaker is not "safer" unless the wire is upsized too, because the breaker must protect the conductor. Motors, heat pumps, air conditioners, welders and other special equipment follow their own rules and nameplate data (for example a maximum overcurrent protection rating).

Common mistakes

Keep in mind: Electrical work is dangerous and regulated. Follow the local electrical code and have installations designed and checked by a licensed electrician.

Frequently asked questions

What size breaker do I need for 15 A continuous?

Under the NEC, 125% × 15 = 18.75 A, so a 20 A breaker.

Why only 80% loading?

Standard breakers are not rated to carry 100% of their rating continuously; the 125% rule keeps them at 80% or less.

Can I use a bigger breaker to stop nuisance trips?

Not unless the wire and equipment are rated for it; an oversized breaker may not protect the wire from overheating.

Sources: NFPA 70, National Electrical Code, sections 210.20(A) and 240.6(A) · 한국전기설비규정(KEC), 저압 전기설비 과전류 보호

Checked 9 Nov 2026. NFPA 70, National Electrical Code: 240.6(A) standard ampere ratings and the 125% continuous-load rule (210.20(A)), as summarised by T. Crnko, “Overcurrent Protection, Part 2”, IAEI Magazine, May 2007. Load-current formulas: US DOE Motor Challenge fact sheet DOE/GO-10097-517.