LMTD Heat Exchanger Calculator

Results update as you type.

Your numbers

Understanding the LMTD heat exchanger calculator — concept and principle

The log mean temperature difference (LMTD) is the effective average temperature difference that drives heat between the hot and cold streams of a heat exchanger. Engineers use it to size exchangers: once the LMTD and the overall heat transfer coefficient U are known, the required area follows from the heat duty.

Counter-flow heat exchanger temperaturesHot water 90 → 55 °C meets cold water 20 → 50 °C flowing the other way; the end differences are 40 K and 35 K, so LMTD = 37.44 K and 500 × 37.44 = 18,722 W/m².Counter-flow: the streams pass each otherhot water →← cold water90 °C55 °C50 °C20 °CΔT₁= 40 KΔT₂= 35 K90 − 50 = 4055 − 20 = 35LMTD = (ΔT₁ − ΔT₂) ÷ ln(ΔT₁ ÷ ΔT₂)5 ÷ ln(40 ÷ 35) = 37.44 KU × LMTD = 500 × 37.44= 18,722 W per m² → 100 kW needs 5.34 m²
Take the temperature gap at each end (40 K and 35 K); their log mean is 37.44 K.

How it is calculated

LMTD = (ΔT₁ − ΔT₂) / ln(ΔT₁/ΔT₂), and Q = U · A · LMTD, so A = Q / (U · LMTD).

If ΔT₁ = ΔT₂ the formula becomes 0/0; the limit is simply that common value, which the calculator uses. The second output, U × LMTD, is the heat transferred per square metre of area.

The principle

Along the exchanger the temperature gap between the streams changes continuously, so the local heat flux changes too. Assuming constant U and constant specific heats, each stream's temperature varies such that the gap changes exponentially with area. Integrating the local heat flux over the whole area gives exactly the logarithmic mean of the end differences, which is always smaller than the arithmetic mean.

Worked example

  1. Inputs: hot 90 → 55 °C, cold 20 → 50 °C, U = 500 W/m²K, counter-flow.
  2. ΔT₁ = 90 − 50 = 40 K; ΔT₂ = 55 − 20 = 35 K.
  3. LMTD = (40 − 35) ÷ ln(40 ÷ 35) = 5 ÷ 0.133531 = 37.44437845 K, a little below the arithmetic mean of 37.5 K.
  4. Heat per m²: 500 × 37.444 = 18,722.18922 W/m².
  5. For a duty of, say, 100 kW, the area would be 100,000 / 18,722 ≈ 5.34 m².
How LMTD (K) changes with Cold in (°C)How LMTD changes with Cold in25303540455101520253040Example: 37.44437845Cold in (°C)
Each point is the calculator re-run with only “Cold in (°C)” changed; the gold point is the default example. Change the inputs above and this chart follows your numbers.
Cold in (°C)LMTD (K)
544.81420118
1042.45093508
1540
2037.44437845
2534.76059497
3031.91464718
4025.4886362

How to read the result

A higher LMTD means a smaller exchanger for the same duty. With the same terminal temperatures, parallel flow gives ΔT₁ = 70 K and ΔT₂ = 5 K, so LMTD ≈ 24.63 K, which needs about 52% more area than counter-flow. In parallel flow the cold outlet can never exceed the hot outlet, whereas counter-flow allows the cold stream to leave hotter than the hot stream leaves.

Common mistakes

Keep in mind: LMTD assumes steady operation, constant U and specific heats, and no phase change across a varying range. Real exchanger design requires the relevant codes and a qualified engineer.

Frequently asked questions

When should I use ε-NTU instead of LMTD?

When the outlet temperatures are unknown. LMTD is easiest when all four temperatures are known and you need the area.

Why not simply use the arithmetic mean?

It overestimates the driving force when the end differences are very different, leading to an undersized exchanger.

What is a typical U?

It depends strongly on fluids and fouling, from tens of W/m²K for gas-to-gas units to a few thousand for water-to-water or condensing service.

Sources: Incropera, DeWitt, Bergman and Lavine, Fundamentals of Heat and Mass Transfer, Wiley · Kern, Process Heat Transfer, McGraw-Hill

Checked 8 Nov 2026. Standard textbook formulas in SI units, computed in your browser. For learning and estimates — real designs must follow your local codes and be checked by a qualified engineer.