Understanding the relative humidity from dew point calculator — concept and principle

Weather reports, aviation observations and many data loggers give the dew point rather than relative humidity. This calculator converts air temperature and dew point into relative humidity (RH), so you can judge comfort, drying conditions, static risk or the humidity a museum or warehouse is actually experiencing.

Relative humidity from temperature and dew pointThe saturation pressure at the 15 °C dew point (17.02 hPa) divided by that at the 25 °C air temperature (31.60 hPa) gives 53.85% RH.RH = vapour present ÷ vapour possible17.02hPadew point 15 °C= vapour in the air31.60hPaair 25 °C= saturation limit÷=53.85%relative humiditye_s = 6.112 · exp(17.62 T ÷ (243.12 + T))17.02 ÷ 31.60 × 100 = 53.85%same dew point, warmer air → lower RH
The dew point tells how much vapour is there; the air temperature tells how much could be: 53.85%.

How it is calculated

RH = e_s(T_d) / e_s(T) × 100%, where e_s is the saturation vapour pressure from the Magnus formula:

e_s(T) = 6.112 · exp(17.62·T / (243.12 + T)) hPa.

The constant 6.112 cancels in the ratio, so the calculator only needs the two exponential terms.

The principle

The dew point fixes the amount of water vapour actually present: at the dew point that vapour would just saturate the air, so the actual vapour pressure equals e_s(T_d). Relative humidity is the actual vapour pressure divided by the maximum the air could hold at its current temperature, e_s(T). Because saturation pressure grows roughly exponentially with temperature, a fixed gap between temperature and dew point gives a lower RH in warm air than in cold air.

Worked example

  1. Inputs: T = 25 °C, T_d = 15 °C.
  2. e_s(15) = 6.112 · exp(17.62 × 15 / 258.12) = 6.112 · e^1.02394 ≈ 17.017 hPa.
  3. e_s(25) = 6.112 · exp(17.62 × 25 / 268.12) = 6.112 · e^1.64292 ≈ 31.601 hPa.
  4. RH = 17.017 / 31.601 × 100 ≈ 53.85%.
How Relative humidity changes with Air temperature (°C)How Relative humidity changes with Air t…0501001502006.2512.518.82531.237.550Example: 53.85%Air temperature (°C)
Each point is the calculator re-run with only “Air temperature (°C)” changed; the gold point is the default example. Change the inputs above and this chart follows your numbers.
Air temperature (°C)Relative humidity
6.25179.02%
12.5117.62%
18.878.85%
2553.85%
31.237.42%
37.526.43%
5013.78%

How to read the result

Where does your result fall?Too dryMould risk30406070Too drySlightly dryComfortableSlightly humidMould riskYour result: 53.85 % · ComfortableReference: Common indoor humidity comfort range (40–60%)
Where does your result fall?

Indoors, about 40–60% RH is a common comfort target; persistently above about 60–70% raises the risk of mould and dust mites, while below about 30% can feel dry and increase static. As a rule of thumb at room temperature, each 1 °C of spread between temperature and dew point lowers RH by roughly 5–6 percentage points near saturation, though the relation is not linear. If T equals T_d, RH is 100%.

Common mistakes

Keep in mind: The result is only as accurate as the measured dew point and temperature, and the Magnus constants used here are for saturation over liquid water. Wet-bulb readings must first be converted to dew point using a psychrometric method; this calculator takes the dew point directly.

Frequently asked questions

Can I enter a wet-bulb temperature instead of the dew point?

Not directly. The wet-bulb temperature lies between the dew point and the air temperature, so using it as the dew point overestimates RH.

Why does the same dew point feel worse in summer?

A high dew point means sweat evaporates poorly, so the body struggles to shed heat even when RH looks moderate.

Is the result affected by altitude?

RH from this ratio is essentially independent of pressure; the humidity ratio, however, does depend on pressure.

Sources: WMO Guide to Instruments and Methods of Observation (WMO-No. 8), Annex on humidity formulae · ASHRAE Handbook — Fundamentals, Psychrometrics chapter