Understanding the three-phase power calculator — concept and principle
This calculator finds the real power (kW) and apparent power (kVA) of a balanced three-phase load from the line-to-line voltage, line current and power factor, and shows the corresponding phase (line-to-neutral) voltage. It is used to size motors, generators, cables and breakers in industrial and commercial installations and to check what a three-phase supply can deliver.
How it is calculated
- Real power: P = √3 · V_L · I_L · cos φ, divided by 1000 for kW.
- Apparent power: S = √3 · V_L · I_L, divided by 1000 for kVA.
- Phase voltage (star): V_ph = V_L / √3.
- Reactive power: Q = √3 · V_L · I_L · sin φ = √(S² − P²), in kvar.
The principle
A three-phase system has three sinusoidal voltages 120° apart. In a balanced load each phase carries the same power, V_ph · I_ph · cos φ, so the total is three times that. In a star (wye) connection the phase voltage is V_L/√3 and the phase current equals the line current; in a delta connection the phase voltage equals V_L and the phase current is I_L/√3. Either way, 3 · V_ph · I_ph = √3 · V_L · I_L. The √3 comes from the geometry of three phasors 120° apart: the distance between the tips of two unit phasors is √3. A balanced three-phase load also draws constant total power instead of a pulsating one, which is why large motors run smoothly on it.
Worked example
- Inputs: V_L = 400 V, I_L = 32 A, PF = 0.9.
- Apparent power: √3 × 400 × 32 = 22,170 VA = 22.170 kVA.
- Real power: 22,170 × 0.9 = 19,953 W = 19.953 kW.
- Phase voltage: 400 ÷ √3 = 230.94 V, the familiar 230 V of a 400 V system.
- Reactive power: sin φ = √(1 − 0.81) = 0.43589, so Q = 22.170 × 0.43589 = 9.663788077 kvar.
| Line-to-line voltage (V) | Real power (kW) |
|---|---|
| 100 | 4.988306326 |
| 200 | 9.976612652 |
| 300 | 14.96491898 |
| 400 | 19.9532253 |
| 500 | 24.94153163 |
| 600 | 29.92983795 |
| 800 | 39.90645061 |
How to read the result
Compare the kVA with the rating of the transformer, generator or UPS and the current with the breaker and cable rating. Common low-voltage systems are 400/230 V (Europe and many other countries, including 380/220 V in Korea) and 208/120 V or 480/277 V in North America. A low power factor raises current for the same kW.
Common mistakes
- Using the phase voltage with the √3 formula, which understates power by a factor of √3. Either use √3 · V_L · I_L or 3 · V_ph · I_ph.
- Applying the formula to a heavily unbalanced load; then each phase must be calculated separately and added.
- Forgetting motor efficiency: a motor's nameplate kW is mechanical output, so its electrical input is larger.
Frequently asked questions
How do I find the current for a given kW?
Rearrange the formula: I = P ÷ (√3 · V_L · PF). For 20 kW at 400 V and PF 0.9, I ≈ 32.1 A.
Is a 400 V three-phase supply more powerful than 230 V single-phase?
For the same current per conductor, yes, it delivers √3 × 400 ÷ 230 ≈ 3 times as much power.
Does star or delta change the power?
Not for the same line voltage and line current; the formula in line quantities is identical.
Sources: IEC 60038, IEC standard voltages · C. K. Alexander and M. N. O. Sadiku, Fundamentals of Electric Circuits, McGraw-Hill, chapter on three-phase circuits