Understanding the voltage regulation calculator — concept and principle
Voltage regulation tells you how much a power source's output voltage falls when it goes from no load to full load. This calculator finds it either from two measured voltages or, for a transformer, from its percentage resistance and reactance and the load power factor. It is used for transformers, generators and power supplies.
How it is calculated
Measured method: VR = (VNL − VFL) ÷ VFL × 100 %
Transformer method: VR ≈ εr cos φ ± εx sin φ + (εx cos φ ∓ εr sin φ)² ÷ 200
Full-load voltage = VNL ÷ (1 + VR ÷ 100)
- VNL no-load voltage, VFL full-load voltage.
- εr and εx are the resistance and reactance drops in % of rated voltage (from the short-circuit test); cos φ is the load power factor. Upper signs apply to lagging (inductive) loads, lower signs to leading (capacitive) loads.
The principle
Every real source has internal impedance. When current flows, part of the source voltage is used up inside, so less reaches the terminals. Regulation expresses that loss relative to the full-load voltage. In a transformer, resistance causes a drop in phase with the current, and leakage reactance causes a drop 90° ahead of it. How these add to the output depends on the load's phase angle: with lagging loads the reactive drop adds strongly, while a leading load can make the output voltage rise, giving negative regulation. The squared term is a small correction for the angle between the voltages.
Worked example
Default inputs: measured method, VNL = 240 V, VFL = 230 V.
- Voltage drop = 240 − 230 = 10 V.
- VR = 10 ÷ 230 × 100 = 4.35 %.
- Full-load voltage = 230 V, which is 230 ÷ 240 × 100 = 95.83 % of no-load.
- The power-factor angle applies only to the transformer method, so it shows —.
| Full-load voltage (V, measured method) | Voltage regulation (%) |
|---|---|
| 57.5 | 317.39 |
| 115 | 108.7 |
| 172 | 39.13 |
| 230 | 4.35 |
| 288 | -16.52 |
| 345 | -30.43 |
| 460 | -47.83 |
How to read the result
Lower regulation means a stiffer source whose voltage holds up under load. Large power transformers typically have low regulation at unity power factor, rising at low lagging power factors. A regulated electronic power supply should be close to 0 %. If regulation is too high for sensitive equipment, consider a larger transformer, tap changing or power-factor correction.
Common mistakes
- Dividing by the no-load voltage instead of the full-load voltage.
- Measuring the two voltages at different input voltages or temperatures.
- Using the wrong sign convention for leading loads.
- Confusing percentage impedance with regulation; they are related but not equal.
Frequently asked questions
Can voltage regulation be negative?
Yes, with a leading (capacitive) load the output voltage can rise above the no-load value.
Why divide by the full-load voltage?
That is the conventional definition; some texts use the no-load voltage, which gives a slightly smaller number.
Where do εr and εx come from?
From the transformer's short-circuit test or nameplate impedance and load-loss data.
Sources: Standard power-engineering formulas: voltage regulation referred to full-load voltage and the transformer approximation from per-unit resistance and reactance