Understanding the wire size calculator — concept and principle

Choosing a cable that is too thin wastes energy and leaves equipment short of voltage. This calculator works backwards from an allowed voltage drop to the minimum conductor cross-section, using the IEC 60364-5-52 method, then rounds up to the next standard metric size (IEC 60228) and the nearest American Wire Gauge, and shows the drop you would actually get.

Wire size from voltage dropPicking a cable for 20 A over 40 mSupply230 V 1-phCurrent20 ALength40 mDrop limit3 %S = 2 × 0.0225 × 40 × 20 ÷ 6.9 VMinimum size5.217 mm²Standard size6 mm² · 2.61 %Then check current rating & breaker
The 3 % drop limit needs 5.2 mm², so the next standard size, 6 mm², is chosen.

How it is calculated

S = b × ρ₁ × L × cos φ × I ÷ (u_allowed − b × λ × L × sin φ × I)

u_allowed = limit × U₀

The principle

The voltage drop in a cable is current times resistance, and resistance is ρL ÷ S. If you fix the largest drop you will accept, you can solve for the area S that just meets it. With AC loads that are not purely resistive, the cable's reactance adds a part that does not depend on S at all, which is why it is subtracted from the allowed drop first. A thicker conductor lowers resistance in direct proportion, so doubling the area halves the resistive part of the drop.

Worked example

Default inputs: single-phase 230 V, 20 A, 40 m, copper, cos φ = 1, limit 3 %.

  1. Allowed drop = 0.03 × 230 = 6.9 V; with cos φ = 1, the reactance term is zero.
  2. S = 2 × 0.0225 × 40 × 1 × 20 ÷ 6.9 = 36 ÷ 6.9 = 5.217 mm².
  3. Next standard size = 6 mm²; nearest AWG with at least this area = 10 AWG (about 5.26 mm²).
  4. Drop with 6 mm²: 2 × 0.0225 × 40 ÷ 6 × 20 = 6.0 V, or 2.61 %.
  5. Check next: current rating & breaker size.
How Minimum cross-section by voltage drop (mm²) changes with Supply voltage (V; line-to-line for three-phase)How Minimum cross-section by voltage dro…051015202557.5115172230288345460Example: 5.217Supply voltage (V; line-to-line for three-phase)
Each point is the calculator re-run with only “Supply voltage (V; line-to-line for three-phase)” changed; the gold point is the default example. Change the inputs above and this chart follows your numbers.
Supply voltage (V; line-to-line for three-phase)Minimum cross-section by voltage drop (mm²)
57.520.87
11510.43
1726.957
2305.217
2884.174
3453.478
4602.609

How to read the result

The size shown is the minimum for voltage drop only. The cable must also carry the current without overheating for its installation method, ambient temperature and grouping, and it must be coordinated with the protective device. The final choice is the larger of the sizes required by all these checks. Typical voltage-drop limits are 3 % for lighting and 5 % for other uses from a public low-voltage supply.

Common mistakes

Keep in mind: Cable sizing must follow local wiring regulations (such as KEC or IEC 60364) and be verified by a qualified electrician or engineer. Undersized cables can overheat and cause fires.

Frequently asked questions

Why round up to a standard size?

Cables are only made in standard cross-sections, so you choose the next one that meets the requirement.

Is 10 AWG the same as 6 mm²?

No. 10 AWG is about 5.26 mm², slightly smaller than 6 mm².

Does aluminium need a larger cable?

Yes, about 1.6 times the copper area for the same voltage drop, because its resistivity is higher.